Breaking Capacity Code Icu @ 415V | H / 70kA |
Poles Description | 3P |
Trip Unit Rating | 48...80 A |
Trip Unit Technology | Thermal-Magnetic |
Control Type | Rocker Lever |
Motor Power @400/415 v | 55KW |
range | TeSys | |
---|---|---|
product name | TeSys GV7 | |
device short name | GV7R | |
product or component type | Circuit breaker | |
device application | Motor | |
poles description | 3P | |
network type | AC | |
utilisation category | AC-3 conforming to IEC 60947-4-1 | |
network frequency | 50/60 Hz conforming to IEC 60947-4-1 | |
breaking capacity | 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 | |
[Ics] rated service short-circuit breaking capacity | 100 % at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
trip unit rating | 90...150 A | |
trip unit technology | Thermal-magnetic |
mounting mode | By clips By screws | |
---|---|---|
mounting support | Flush Panel mounting Rail Kit for fixing the switchgear | |
mounting position | Vertical | |
motor power kW | 110 kW at 660...690 V AC 50/60 Hz 55 kW at 400...415 V AC 50/60 Hz 75 kW at 400...415 V AC 50/60 Hz 75 kW at 500 V AC 50/60 Hz 90 kW at 500 V AC 50/60 Hz 90 kW at 660...690 V AC 50/60 Hz | |
control type | Rocker lever | |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
[Ui] rated insulation voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 | |
[Ith] conventional free air thermal current | 150 A conforming to IEC 60947-4-1 | |
[Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 | |
power dissipation per pole | 8.7 W | |
power dissipation | 8.7 W | |
mechanical durability | 40000 cycles | |
electrical durability | 40000 cycles for AC-3 at 440 V In/2 20000 cycles for AC-3 at 440 V In | |
operating rate | 25 cyc/h | |
rated duty | Continuous conforming to IEC 60947-4-1 | |
connection pitch | 35 mm without spreaders 45 mm with spreaders | |
connections - terminals | Bars Cable with lug - external diameter : 10 mm Bare cable connectors 1.5...95 mm² Screw | |
tightening torque | 10 N.m - on screw - screw M6 15 N.m - on bare cable connectors- cable 1.5...95 mm² | |
mechanical robustness | Shocks 15 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations 2.5 Gn, 0...25 Hz conforming to IEC 60068-2-6 | |
suitability for isolation | Yes conforming to IEC 60947-1 | |
phase failure sensitivity | Yes conforming to IEC 60947-4-1 § 7-2-1-5-2 | |
height | 125 mm | |
width | 105 mm | |
depth | 111 mm | |
product weight | 2.02 kg |
standards | EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-4-1 NF C 63-120 NF C 63-650 NF C 79-130 VDE 0113 VDE 0660 | |
---|---|---|
product certifications | DNV UL | |
protective treatment | TC | |
IP degree of protection | IP405 with terminal shrouds conforming to IEC 60529 | |
pollution degree | 3 | |
ambient air temperature for operation | -25...70 °C | |
ambient air temperature for storage | -55...95 °C | |
fire resistance | 960 °C conforming to IEC 60695-2-1 | |
operating altitude | 2000 m |