| range | TeSys | |
| product name | TeSys GV2 | |
| device short name | GV2LE | |
| product or component type | Circuit breaker | |
| device application | Motor | |
| poles description | 3P | |
| network type | AC | |
| utilisation category | AC-3 conforming to IEC 60947-4-1 Category A conforming to IEC 60947-2 | |
| network frequency | 50/60 Hz conforming to IEC 60947-2 | |
| breaking capacity | 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 40 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
| trip unit rating | 25 A | |
| trip unit technology | Magnetic | |
| magnetic tripping current | 327 A |
| mounting mode | By screws By clips | |
| mounting support | Rail Plate | |
| mounting position | Horizontal Vertical | |
| motor power kW | 11 kW at 400/415 V AC 50/60 Hz 11 kW at 500 V AC 50/60 Hz 15 kW at 500 V AC 50/60 Hz 9 kW at 400/415 V AC 50/60 Hz 18.5 kW at 690 V AC 50/60 Hz | |
| control type | Toggle | |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 | |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 | |
| power dissipation per pole | 1.8 W | |
| mechanical durability | 100000 cycles | |
| electrical durability | 100000 cycles for AC-3 at 415 V | |
| operating rate | 40 cyc/h | |
| rated duty | Continuous conforming to IEC 60947-4-1 | |
| connections - terminals | Screw clamp terminals 2 cable(s) 1...6 mm² - cable stiffness : solid Screw clamp terminals 2 cable(s) 1.5...6 mm² - cable stiffness : flexible - without cable end Screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness : flexible - with cable end | |
| tightening torque | 1.7 N.m - on screw clamp terminals | |
| mechanical robustness | Shocks 30 Gn conforming to IEC 60068-2-27 Vibrations 5 Gn, 5...150 Hz conforming to IEC 60068-2-6 | |
| suitability for isolation | Yes conforming to IEC 60947-1 | |
| height | 89 mm | |
| width | 45 mm | |
| depth | 78.5 mm | |
| product weight | 0.33 kg |
| standards | EN 60204 NF C 79-130 VDE 0660 NF C 63-650 VDE 0113 IEC 60947-1 NF C 63-120 IEC 60947-2 | |
| product certifications | CSA CCC | |
| protective treatment | TH | |
| IK degree of protection | IK04 | |
| ambient air temperature for operation | -20...60 °C | |
| ambient air temperature for storage | -40...80 °C | |
| fire resistance | 960 °C conforming to IEC 60695-2-1 | |
| operating altitude | 2000 m |