Close
LC1D65G7 View larger

LC1D65G7

Square D (Schneider Electric)

Square D (Schneider Electric)

3389110351088

New Factory Sealed - Original product -12 Months Warranty

LC1D65G7 - TeSys D IEC contactor, 65 A, 3 P, 40 HP at 480 VAC, nonreversing, 120 VAC 50/60 Hz coil

More details

10 Items

IN STOCK

$145.36

Usually dispatched 1-2 days

More info

Main
range of product
TeSys D
range
TeSys
product or component type
Contactor
device short name
LC1D
contactor application
Motor control
Resistive load
utilisation category
AC-1
AC-2
AC-4
AC-3
control circuit type
AC at 50/60 Hz
poles description
3P
pole contact composition
3 NO
[Ie] rated operational current
80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
motor power kW
30 kW at 440 V AC 50/60 Hz (AC-3)
11 kW at 400 V AC 50/60 Hz (AC-4)
30 kW at 380...400 V AC 50/60 Hz (AC-3)
30 kW at 415 V AC 50/60 Hz (AC-3)
37 kW at 1000 V AC 50/60 Hz (AC-3)
37 kW at 500 V AC 50/60 Hz (AC-3)
37 kW at 660...690 V AC 50/60 Hz (AC-3)
18.5 kW at 220...230 V AC 50/60 Hz (AC-3)
motor power hp
10 hp at 230/240 V AC 60 Hz for 1P motors conforming to CSA
10 hp at 230/240 V AC 60 Hz for 1P motors conforming to UL
20 hp at 200/208 V AC 60 Hz for 3P motors conforming to CSA
20 hp at 200/208 V AC 60 Hz for 3P motors conforming to UL
20 hp at 230/240 V AC 60 Hz for 3P motors conforming to CSA
20 hp at 230/240 V AC 60 Hz for 3P motors conforming to UL
5 hp at 115 V AC 60 Hz for 1P motors conforming to CSA
5 hp at 115 V AC 60 Hz for 1P motors conforming to UL
50 hp at 460/480 V AC 60 Hz for 3P motors conforming to CSA
50 hp at 460/480 V AC 60 Hz for 3P motors conforming to UL
50 hp at 575/600 V AC 60 Hz for 3P motors conforming to CSA
50 hp at 575/600 V AC 60 Hz for 3P motors conforming to UL
[Uc] control circuit voltage
120 V AC 50/60 Hz
connections - terminals
Control circuit: screw clamp terminal 1 x 1…4 mm²solid without cable end
Control circuit: screw clamp terminal 2 x 1…4 mm²solid without cable end
Control circuit: screw clamp terminal 1 x 1…4 mm²flexible with cable end
Control circuit: screw clamp terminal 2 x 1…2.5 mm²flexible without cable end
Power circuit: screw terminals
Power circuit: screw clamp terminal 2 x 1…25 mm²solid without cable end
Control circuit: screw clamp terminal 2 x 1…4 mm²flexible with cable end
Power circuit: screw clamp terminal 1 x 1…35 mm²flexible without cable end
Power circuit: screw clamp terminal 1 x 1…35 mm²solid without cable end
Power circuit: screw clamp terminal 2 x 1…25 mm²flexible with cable end
Power circuit: screw clamp terminal 2 x 1…35 mm²flexible without cable end
Power circuit: screw clamp terminal 2 x 1…35 mm²solid with cable end
Complementary
coil technology
Without built-in bidirectional peak limiting diode suppressor
protective cover
With
auxiliary contacts type
type mirror contact 1 NC conforming to IEC 60947-4-1
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
auxiliary contact composition
1 NO + 1 NC
control circuit voltage limits
Drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C)
Operational: 0.8...1.1 Uc at 50 Hz (at <60 °C)
Operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
[Ui] rated insulation voltage
Control circuit: 600 V CSA certified
Control circuit: 600 V UL certified
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Control circuit: 690 V conforming to IEC 60947-1
Power circuit: 690 V conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947
overvoltage category
III
mounting support
Rail
Plate
flame retardance
V1 conforming to UL 94
tightening torque
Control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m - on screw clamp terminal - with screwdriver Philips No 2
Power circuit: 5 N.m - on screw clamp terminal - with screwdriver flat Ø 6 mm
Power circuit: 5 N.m - on screw clamp terminal - with screwdriver flat Ø 8 mm
[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
[Ith] conventional free air thermal current
10 A (at 60 °C) for control circuit
80 A (at 60 °C) for power circuit
Irms rated making capacity
140 A AC for control circuit conforming to IEC 60947-5-1
1000 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity
1000 A at 440 V for power circuit conforming to IEC 60947
associated fuse rating
10 A gG for control circuit conforming to IEC 60947-5-1
125 A gG at <= 690 V coordination type 1 for power circuit
125 A gG at <= 690 V coordination type 2 for power circuit
average impedance
- Ith 80 A 50 Hz for power circuit
power dissipation per pole
6.4 W AC-1
inrush power in VA
140 VA cos phi 0.75 (at 20 °C)
160 VA cos phi 0.75 (at 20 °C)
hold-in power consumption in VA
13 VA 50 Hz cos phi 0.3 (at 20 °C)
15 VA 60 Hz cos phi 0.3 (at 20 °C)
operating time
12...26 ms closing
4...19 ms opening
safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability
6000000 cycles
maximum operating rate
3600 cyc/h 60 °C
minimum switching current
5 mA for control circuit
minimum switching voltage
17 V for control circuit
non-overlap time
1.5 ms on de-energisation between NC and NO contacts
1.5 ms on energisation between NC and NO contacts
insulation resistance
> 10 MOhm for control circuit
terminals description ISO n°1
(A1-A2)CO
(13-14)NO
(21-22)NC
height
127 mm
width
75 mm
depth
119 mm
net weight
1.4 kg
Environment
standards
EN 60947-5-1
CSA C22.2 No 14
EN 60947-4-1
UL 508
IEC 60947-4-1
IEC 60947-5-1
product certifications
CCC
UL
BV
CSA
LROS (pending)
GOST
RINA
GL
DNV
IP degree of protection
IP2x conforming to IEC 60529
IP2x conforming to VDE 0106
ambient air temperature for operation
-5…60 °C
ambient air temperature for storage
-60…80 °C
permissible ambient air temperature around the device
-40…70 °C at Uc
operating altitude
3000 m without
fire resistance
850 °C conforming to IEC 60695-2-1
shock resistance
10 gn contactor opened
15 gn contactor closed
vibration resistance
2 gn 5…300 Hz contactor opened
4 gn 5…300 Hz contactor closed
heat dissipation
4…5 W at 50/60 Hz for control circuit
Offer Sustainability
Sustainable offer status
Green Premium product
REACh Regulation
EU RoHS Directive
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
China RoHS Regulation
Environmental Disclosure
Circularity Profile
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Contractual warranty
Warranty
18 months

30 other products in the same category

Schneider Partner

Schneider Electric Authorised distributor

Shipping Partner

DHL Express Delivery

Secure Payments

Scure site globalsign

Close