Product successfully added to your shopping cart
Quantity:
Total
There are 0 items in your cart. There is 1 item in your cart.
Total products:
Total shipping: To be determined
Total:
3389110357257
New Factory Sealed - Original product -12 Months Warranty
20 Item Items
IN STOCK
Warning: Last items in stock!
Availability date:
range | TeSys | |
---|---|---|
product name | TeSys D | |
product or component type | Contactor | |
device short name | LC1D | |
contactor application | Resistive load Motor control | |
utilisation category | AC-3 AC-1 AC-4 | |
poles description | 3P | |
power pole contact composition | 3 NO | |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 25...400 Hz Power circuit: <= 300 V DC | |
[Ie] rated operational current | 32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit | |
motor power kW | 7.5 kW at 220...230 V AC 50/60 Hz (AC-3) 15 kW at 380...400 V AC 50/60 Hz (AC-3) 15 kW at 415...440 V AC 50/60 Hz (AC-3) 18.5 kW at 500 V AC 50/60 Hz (AC-3) 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) 7.5 kW at 400 V AC 50/60 Hz (AC-4) | |
motor power HP (UL / CSA) | 2 hp at 115 V AC 50/60 Hz for 1 phase motors 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors 7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors 20 hp at 460/480 V AC 50/60 Hz for 3 phases motors 30 hp at 575/600 V AC 50/60 Hz for 3 phases motors | |
control circuit type | DC standard | |
[Uc] control circuit voltage | 24 V DC | |
auxiliary contact composition | 1 NO + 1 NC | |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 | |
overvoltage category | III | |
[Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit 50 A (at 60 °C) for power circuit | |
Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 550 A at 440 V for power circuit conforming to IEC 60947 | |
rated breaking capacity | 550 A at 440 V for power circuit conforming to IEC 60947 | |
[Icw] rated short-time withstand current | 260 A 40 °C - 10 s for power circuit 430 A 40 °C - 1 s for power circuit 60 A 40 °C - 10 min for power circuit 138 A 40 °C - 1 min for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit | |
associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 63 A gG at <= 690 V coordination type 1 for power circuit 63 A gG at <= 690 V coordination type 2 for power circuit | |
average impedance | 2 mOhm - Ith 50 A 50 Hz for power circuit | |
[Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified | |
electrical durability | 1.65 Mcycles 32 A AC-3 at Ue <= 440 V 1.4 Mcycles 50 A AC-1 at Ue <= 440 V | |
power dissipation per pole | 2 W AC-3 5 W AC-1 | |
safety cover | With | |
mounting support | Rail Plate | |
standards | CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 | |
product certifications | DNV GL CCC UL GOST BV LROS (Lloyds register of shipping) RINA CSA | |
connections - terminals | Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm²flexible without cable end Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 1…10 mm²flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm²solid without cable end Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²solid without cable end | |
tightening torque | Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2 | |
operating time | 53.55...72.45 ms closing 16...24 ms opening | |
safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 | |
mechanical durability | 30 Mcycles | |
maximum operating rate | 3600 cyc/h 60 °C |
coil technology | Built-in bidirectional peak limiting diode suppressor | |
---|---|---|
control circuit voltage limits | Drop-out: 0.1...0.25 Uc DC (at 60 °C) Operational: 0.7...1.25 Uc DC (at 60 °C) | |
time constant | 28 ms | |
inrush power in W | 5.4 W (at 20 °C) | |
hold-in power consumption in W | 5.4 W at 20 °C | |
auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 | |
signalling circuit frequency | 25...400 Hz | |
minimum switching current | 5 mA for signalling circuit | |
minimum switching voltage | 17 V for signalling circuit | |
non-overlap time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact | |
insulation resistance | > 10 MOhm for signalling circuit |
IP degree of protection | IP20 front face conforming to IEC 60529 | |
---|---|---|
protective treatment | TH conforming to IEC 60068-2-30 | |
pollution degree | 3 | |
ambient air temperature for operation | -5…60 °C | |
ambient air temperature for storage | -60…80 °C | |
permissible ambient air temperature around the device | -40…70 °C at Uc | |
operating altitude | 3000 m without | |
fire resistance | 850 °C conforming to IEC 60695-2-1 | |
flame retardance | V1 conforming to UL 94 | |
mechanical robustness | Vibrations contactor open: 2 Gn, 5...300 Hz Vibrations contactor closed: 4 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Shocks contactor open: 8 Gn for 11 ms | |
height | 85 mm | |
width | 45 mm | |
depth | 101 mm | |
net weight | 0.535 kg |
Sustainable offer status | Green Premium product | |
---|---|---|
REACh Regulation | ||
EU RoHS Directive | Compliant EU RoHS Declaration | |
Mercury free | Yes | |
RoHS exemption information | ||
China RoHS Regulation | China RoHS declaration Product out of China RoHS scope. Substance declaration for your information | |
Environmental Disclosure | ||
Circularity Profile | ||
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
Warranty | 18 months |
---|