Close
LV430391 View larger

LV430391

Square D (Schneider Electric)

249_1890216602

Square D (Schneider Electric)

3606480006685

New Factory Sealed - Original product -12 Months Warranty

circuit breaker Compact NSX160S - 160 A - 3 poles - without trip unit

More details

25 Items

IN STOCK

$527.36 TAX INCLUDED

Usually dispatched 1-2 days

Data sheet

Breaking Capacity Code Icu @ 415VS / 100 kA
Poles Description3P
[In] Rated Current160 A

More info

Characteristics
Main
Commercial StatusCommercialised 
Range of productNSX100...250 
Device short nameCompact NSX160S 
Circuit breaker nameCompact NSX160S 
Poles description3P 
[In] rated current160 A ( 40 °C ) 
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2 
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code
Breaking capacityIcu 90 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 
Icu 65 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 
Icu 40 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 
Icu 15 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 
Icu 120 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 
Icu 100 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 
90 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 
40 kA at 600 V AC 50/60 Hz conforming to NEMA AB1 
120 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 
[Ics] rated service breaking capacityIcs 90 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 
Ics 65 kA 500 V AC 50/60 Hz conforming to IEC 60947-2 
Ics 40 kA 525 V AC 50/60 Hz conforming to IEC 60947-2 
Ics 15 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2 
Ics 120 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2 
Ics 100 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 
Suitability for isolationYes conforming to IEC 60947-2 
Yes conforming to EN 60947-2 
Pollution degree3 conforming to IEC 60947-1 
Complementary
Control typeToggle 
Mounting modeFixed 
Mechanical durability40000 cycles conforming to IEC 60947-2 
Electrical durability7500 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 
20000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 
15000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 
10000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 
Environment
IP degree of protectionIP40 conforming to IEC 60529 
IK degree of protectionIK07 conforming to IEC 62262 

30 other products in the same category

Accessories

Schneider Partner

Schneider Electric Authorised distributor

Shipping Partner

DHL Express Delivery

Secure Payments

Scure site globalsign

Close