| Device Short Name | PM3000 |
| Display Type | Backlit LCD |
| Power Quality Analysis | Up to the 15th harmonic |
| Sample Rate | 32 samples/cycle |
| range | PowerLogic | |
|---|---|---|
| product name | PowerLogic PM3000 | |
| device short name | PM3250 | |
| product or component type | Power meter |
| power quality analysis | Up to the 15th harmonic | |
|---|---|---|
| device application | Power monitoring Sub billing Multi-tariff | |
| type of measurement | Energy Active and reactive power Total current harmonic distortion THD (I) Total voltage harmonic distortion THD (U) Voltage Current Frequency Power factor Apparent power | |
| supply voltage | 100...300 V DC 100...277 V AC (45...65 Hz) 173...480 V AC (45...65 Hz) | |
| network frequency | 50 Hz 60 Hz | |
| Line Rated Current | 1 A 5 A | |
| type of network | 1P + N 3P 3P + N | |
| power consumption in VA | 5 VA | |
| display type | Backlit LCD | |
| display resolution | 128 x 96 pixels | |
| sampling rate | 32 samples/cycle | |
| measurement current | 0.05...6 A 0.02...1.2 A | |
| analogue input type | Current 0...5 A Current 0...1 A | |
| measurement voltage | 50...330 V AC 45...65 Hz direct 50...330 V AC 45...65 Hz phase to neutral 80...570 V AC 45...65 Hz direct 80...570 V AC 45...65 Hz phase to phase 570...999000 V AC 45...65 Hz with external VT | |
| frequency measurement range | 45...65 Hz | |
| number of inputs | 0 | |
| measurement accuracy | 0.3 % current (0.5...6 A) 0.5 % current (0.1...1.2 A) 0.3 % voltage (50...330 V) 0.3 % voltage (80...570 V) | |
| accuracy class | Class 0.5S (active energy according to IEC 62053-22) Class 2 (reactive energy according to IEC 62053-23) Class 1 (active energy according to IEC 62053-21) Class C (active energy according to EN 50470-3) | |
| number of outputs | 0 | |
| information displayed | Tariff 4 | |
| communication port protocol | Modbus : 9.6...38.4 kbauds, | |
| communication port support | RS485 | |
| data recording | Min/max of instantaneous values Time stamping 5 alarms | |
| mounting mode | Clip-on | |
| mounting support | DIN rail | |
| standards | EN 61010-1 IEC 61557-12 IEC 62052-11 EN 50470-1 EN 50470-3 EN 61557-12 UL 61010-1 | |
| product certifications | CULus conforming to UL 61010-1 UL CE conforming to EN 61010-1 | |
| width | 3.54 in (90 mm) | |
| depth | 2.76 in (70 mm) | |
| height | 3.74 in (95 mm) | |
| product weight | 0.57 lb(US) (0.26 kg) |
| electromagnetic compatibility | ● conducted and radiated emissions class class B, conforming to EN 55022 ● electrostatic discharge class level 4, conforming to IEC 61000-4-2 ● conducted RF disturbances class level 3, conforming to IEC 61000-4-6 ● electrical fast transient/burst immunity test class level 4, conforming to IEC 61000-4-4 ● susceptibility to electromagnetic fields class level 3, conforming to IEC 61000-4-3 ● 1.2/50 µs shock waves immunity test class level 4, conforming to IEC 61000-4-5 ● magnetic field at power frequency (0.5 mT ), conforming to IEC 61000-4-8 | |
|---|---|---|
| overvoltage category | III | |
| IP degree of protection | IP20 (body) conforming to IEC 60529 IP40 (front panel) conforming to IEC 60529 | |
| relative humidity | 5...95 % 122 °F (50 °C) | |
| pollution degree | 2 | |
| ambient air temperature for operation | -13...131 °F (-25...55 °C) | |
| ambient air temperature for storage | -40...185 °F (-40...85 °C) | |
| operating altitude | 0...9842.52 ft (0...3000 m) |
| Category | 09786 - SE ENTRY POWER METER | |
|---|---|---|
| Discount Schedule | PL1 | |
| GTIN | 00785901009979 | |
| Nbr. of units in pkg. | 1 | |
| Package weight(Lbs) | 8.0000000000000002E-2 | |
| Returnability | N | |
| Country of origin | CN |
| Sustainable offer status | Green Premium product | |
|---|---|---|
| RoHS (date code: YYWW) | ||
| REACh | ||
| Product environmental profile | Available | |
| Product end of life instructions | Available | |
| California proposition 65 | WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov |
| Warranty period | 18 months |
|---|
![]()