Circuit breaker Compact NSX400H - 400 A - 3 poles - without trip unit

More details

20 Items

IN STOCK

$843.95

Usually dispatched 1-2 days

Data sheet

Breaking Capacity Code Icu @ 415VH / 70kA
Poles Description3P
[In] Rated Current400 A

More info

Characteristics
Main
Commercial StatusCommercialised?
Range of productNSX400...630?
Device short nameCompact NSX400H?
Circuit breaker nameCompact NSX400H?
Poles description3P?
Network typeAC?
Network frequency50/60 Hz?
[In] rated current400 A ( 40 ?C )?
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2?
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH?
Breaking capacity20 kA at 600 V AC 50/60 Hz conforming to UL 508?
Icu 20 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2?
Icu 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2?
Icu 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2?
Icu 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2?
Icu 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2?
Icu 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2?
65 kA at 480 V AC 50/60 Hz conforming to UL 508?
65 kA at 480 V AC 50/60 Hz conforming to NEMA AB1?
35 kA at 600 V AC 50/60 Hz conforming to NEMA AB1?
100 kA at 240 V AC 50/60 Hz conforming to NEMA AB1?
85 kA at 240 V AC 50/60 Hz conforming to UL 508?
[Ics] rated service breaking capacityIcs 70 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2?
Ics 65 kA 440 V AC 50/60 Hz conforming to IEC 60947-2?
Ics 50 kA 500 V AC 50/60 Hz conforming to IEC 60947-2?
Ics 100 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2?
Ics 10 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2?
Ics 11 kA 525 V AC 50/60 Hz conforming to IEC 60947-2?
Suitability for isolationYes conforming to IEC 60947-2?
Yes conforming to EN 60947-2?
Utilisation categoryCategory A?
Pollution degree3 conforming to IEC 60947-1?
Complementary
Control typeToggle?
Mounting modeFixed?
Mounting supportBackplate?
Upside connectionFront?
Downside connectionFront?
Mechanical durability15000 cycles conforming to IEC 60947-2?
Electrical durability6000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2?
6000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2?
3000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2?
12000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2?
Connection pitch45 mm?
Height255 mm?
Width140 mm?
Depth110 mm?
Environment
StandardsEN 60947-2?
IEC 60947-2?
NEMA AB1?
UL 508?
Product certificationsCSA?
UL?
IP degree of protectionIP40 conforming to IEC 60529?
IK degree of protectionIK07 conforming to IEC 62262?
Ambient air temperature for operation-35...70 ?C?
Ambient air temperature for storage-55...85 ?C?

30 other products in the same category

Schneider Partner

Schneider Electric Authorised distributor

Shipping Partner

DHL Express Delivery

Secure Payments

Scure site globalsign