Circuit breaker Compact NSX100F - TMD - 40 A - 3 poles 3d

More details

24 Items

IN STOCK

$338.63

Usually dispatched 1-2 days

Data sheet

Breaking Capacity Code Icu @ 415VF / 36kA
Poles Description3P
Trip Unit Rating40 A
Trip Unit NameTM-D
[In] Rated Current100 A
Trip Unit TechnologyThermal-Magnetic
Protected Poles3t

More info

Characteristics
Main
Commercial StatusCommercialised?
Product or component typeCircuit breaker?
Device short nameCompact NSX100F?
Circuit breaker applicationDistribution?
Poles description3P?
Protected poles description3t?
Network typeAC?
Network frequency50/60 Hz?
[In] rated current100 A ( 40 ?C )?
[Ui] rated insulation voltage800 V AC 50/60 Hz?
[Uimp] rated impulse withstand voltage8 kV?
[Ue] rated operational voltage690 V AC 50/60 Hz?
Breaking capacity codeF?
Breaking capacityIcu 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2?
Icu 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2?
Icu 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2?
Icu 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2?
Icu 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2?
Icu 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2?
85 kA at 240 V AC 50/60 Hz conforming to UL 508?
85 kA at 240 V AC 50/60 Hz conforming to NEMA AB1?
8 kA at 600 V AC 50/60 Hz conforming to NEMA AB1?
35 kA at 480 V AC 50/60 Hz conforming to NEMA AB1?
25 kA at 480 V AC 50/60 Hz conforming to UL 508?
10 kA at 600 V AC 50/60 Hz conforming to UL 508?
[Ics] rated service breaking capacityIcs 12.5 kA 500 V AC 50/60 Hz conforming to IEC 60947-2?
Ics 85 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2?
Ics 4 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2?
Ics 36 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2?
Ics 35 kA 440 V AC 50/60 Hz conforming to IEC 60947-2?
Ics 11 kA 525 V AC 50/60 Hz conforming to IEC 60947-2?
Suitability for isolationYes conforming to IEC 60947-2?
Yes conforming to EN 60947-2?
Utilisation categoryCategory A?
Trip unit nameTM-D?
Trip unit technologyThermal-magnetic?
Trip unit protection functionsLI?
Trip unit rating40 A ( 40 ?C )?
Protection typeOverload protection (thermal)?
Short-circuit protection (magnetic)?
Pollution degree3 conforming to IEC 60664-1?
Complementary
Control typeToggle?
Mounting modeFixed?
Mounting supportBackplate?
Upside connectionFront?
Downside connectionFront?
Mechanical durability50000 cycles?
Electrical durability50000 cycles 440 V In/2 conforming to IEC 60947-2?
30000 cycles 440 V In conforming to IEC 60947-2?
20000 cycles 690 V In/2 conforming to IEC 60947-2?
10000 cycles 690 V In conforming to IEC 60947-2?
Connection pitch35 mm?
Local signallingPositive contact indication?
Long time pick-up adjstment type IrAdjustable?
Long time pick-up adjustment range0.7...1 x In?
Long time delay adjustment typeFixed?
[tr] long-time delay adjustment15 s 6 x Ir?
120...400 s 1.5 x In?
Short-time pick-up adjustment type IsdFixed?
[Isd] short-time pick-up adjustment range800 A?
Short-time delay adjustment typeFixed?
Height161 mm?
Width105 mm?
Depth86 mm?
Product weight2.05 kg?
Environment
Electrical shock protection classClass II?
StandardsEN 60947-2?
IEC 60947-2?
NEMA AB1?
UL 508?
Product certificationsCSA?
UL?
IP degree of protectionIP40 conforming to IEC 60529?
IK degree of protectionIK07 conforming to IEC 62262?
Ambient air temperature for operation-35...70 ?C?
Ambient air temperature for storage-55...85 ?C?

30 other products in the same category