Close
LV432090 View larger

LV432090

Square D (Schneider Electric)

438_700651324

Square D (Schneider Electric)

3606480016783

New Factory Sealed - Original product -12 Months Warranty

trip unit - Micrologic 5.3 A - 630 A - 3 poles 3d

More details

24 Items

IN STOCK

$1,728.67 TAX INCLUDED

Usually dispatched 1-2 days

Data sheet

Poles Description3P
Trip Unit Rating630 A
Trip Unit NameMicrologic 5.2 A
Trip Unit TechnologyElectronic
Protected Poles3t
Frame TypeNSX 400/630 A

More info

Characteristics
Main
Commercial StatusCommercialised 
Range of productNSX400...630 
Circuit breaker applicationDistribution 
Poles description3P 
Protected poles description3t 
Network typeAC 
Network frequency50/60 Hz 
Trip unit nameMicrologic 5.3 A 
Trip unit technologyElectronic 
Trip unit protection functionsLSI 
Trip unit rating630 A ( 40 °C ) 
Protection typeInstantaneous short-circuit protection 
Overload protection (long time) 
Short time short-circuit protection 
Complementary
Mounting modeFixed 
[Ue] rated operational voltage690 V AC 50/60 Hz 
Long time pick-up adjstment type IrAdjustable 
Long time pick-up adjustment range160...400 A 
Long time delay adjustment typeAdjustable 
[tr] long-time delay adjustment0.5...16 s 6 x Ir 
0.35...11 s 7.2 x Ir 
15...400 s 1.5 x Ir 
Thermal memory20 minutes before and after tripping 
Short-time pick-up adjustment type IsdAdjustable 
[Isd] short-time pick-up adjustment range1.5...10 x Ir 
Short-time delay adjustment typeAdjustable 
[tsd] short-time delay adjustment range0...0.4 s 
Instantaneous pick-up adjustment type IiAdjustable 
Instantaneous pick-up adjustment range1.5...12 x In Compact NSX400 
1.5...11 x In Compact NSX630 
Zone selective interlocking ZSIWith 
Communication of dataDemand current and power 
Energy metering 
Instantaneous and demand values 
Maintenance indicators 
Maximeters/minimeters 
Power quality 
Protection and alarm settings 
Time-stamped histories and event tables 
Display typeLCD display 
Type of measurementAmmeter 
Electrical data recordingMaintenance indicators 
Environment
StandardsEN 60947-2 
IEC 60947-2 
NEMA AB1 
UL 508 
Product certificationsCSA 
UL 
IP degree of protectionIP40 conforming to IEC 60529 
Pollution degree3 conforming to IEC 60947-1 
Ambient air temperature for operation-25...70 °C 
Ambient air temperature for storage-40...85 °C 