Main
range
ComPact
product name
ComPact NSX
range of product
ComPact NSX100...250
device short name
NSX160F
product or component type
Circuit breaker
device application
Distribution
Number of poles
3P
protected poles description
3t
[In] rated current
160 A at 40 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
network type
AC
network frequency
50/60 Hz
suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
10 kA at 600 V AC 50/60 Hz conforming to UL 508
85 kA at 240 V AC 50/60 Hz conforming to UL 508
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 480 V AC 50/60 Hz conforming to UL 508
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Performance level
F 36 kA 415 V AC
trip unit name
Micrologic 2.2
trip unit technology
Electronic
trip unit protection functions
LSoI
control type
Toggle
Circuit breaker mounting mode
Fixed
Complementary
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ics] rated service short-circuit breaking capacity
35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability
40000 cycles
electrical durability
7500 cycles at 690 V In
15000 cycles at 690 V In/2
20000 cycles at 440 V In
40000 cycles at 440 V In/2
mounting support
Backplate
upside connection
Front
downside connection
Front
connection pitch
35 mm
protection type
L : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection
trip unit rating
160 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
63...160 A
Long-time protection delay adjustment type tr
Fixed
[tr] long-time protection delay adjustment range
11 s at 7.2 x Ir
16 s at 6 x Ir
400 s at 1.5 x Ir
thermal memory
20 minutes before and after tripping
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5...10 x Ir
Short-time protection delay adjustment type tsd
Fixed
Instantaneous protection pick-up adjustment type Ii
Fixed
[Ii] instantaneous protection pick-up adjustment range
2400 A
earth-leakage protection
Without
Number of slots for electrical auxiliaries
5 slot(s)
local signalling
Flashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload
Width (W)
105 mm
Height (H)
161 mm
Depth (D)
86 mm
net weight
2.2 kg
Environment
standards
EN/IEC 60947
product certifications
CCC
EAC
Marine
overvoltage category
Class II
electrical shock protection class
Class II
pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
ambient air temperature for operation
-25…70 °C
ambient air temperature for storage
-50…85 °C
relative humidity
0…95 %
operating altitude
0...2000 m without derating
2000 m...5000 m with derating
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Weight
1.86 kg
Package 1 Height
11.6 cm
Package 1 width
14.2 cm
Package 1 Length
19.3 cm
EAN13 3606480009945
Poles Description
3P
Trip Unit Rating
160 A
Trip Unit Name
Micrologic 2.2
[In] Rated Current
160 A
Trip Unit Technology
Electronic
Breaking Capacity Code Icu @ 415V
F / 36kA
Frame Type
NSX 160 A

Returns Policy

You may return most new, unopened items within 30 days of delivery for a full refund. We'll also pay the return shipping costs if the return is a result of our error (you received an incorrect or defective item, etc.).

You should expect to receive your refund within four weeks of giving your package to the return shipper, however, in many cases you will receive a refund more quickly. This time period includes the transit time for us to receive your return from the shipper (5 to 10 business days), the time it takes us to process your return once we receive it (3 to 5 business days), and the time it takes your bank to process our refund request (5 to 10 business days).

If you need to return an item, simply login to your account, view the order using the 'Complete Orders' link under the My Account menu and click the Return Item(s) button. We'll notify you via e-mail of your refund once we've received and processed the returned item.

Shipping

We can ship to virtually any address in the world. Note that there are restrictions on some products, and some products cannot be shipped to international destinations.

When you place an order, we will estimate shipping and delivery dates for you based on the availability of your items and the shipping options you choose. Depending on the shipping provider you choose, shipping date estimates may appear on the shipping quotes page.

Please also note that the shipping rates for many items we sell are weight-based. The weight of any such item can be found on its detail page. To reflect the policies of the shipping companies we use, all weights will be rounded up to the next full pound.

  • "Excellent products and excellent service." - Josephine
  • "Excellent value. High quality products at reasonable prices." - Warren
  • "Outstanding customer service." - Jack
  • "You're the best! Thank you!" - Tatiana