LC1D123FD
LC1D123FD - TeSys D contactor - 3P(3 NO) - AC-3 - 440 V 12 A - 110 V DC coil
| range |
TeSys
|
|
|---|---|---|
| product name |
TeSys D
|
|
| product or component type |
Contactor
|
|
| device short name |
LC1D
|
|
| contactor application |
Motor control
Resistive load |
|
| utilisation category |
AC-1
AC-3 AC-4 |
|
| poles description |
3P
|
|
| power pole contact composition |
3 NO
|
|
| [Ue] rated operational voltage |
Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC |
|
| [Ie] rated operational current |
16 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit |
|
| motor power kW |
3 kW at 220...230 V AC 50/60 Hz (AC-3)
5.5 kW at 380...400 V AC 50/60 Hz (AC-3) 5.5 kW at 415...440 V AC 50/60 Hz (AC-3) 7.5 kW at 500 V AC 50/60 Hz (AC-3) 7.5 kW at 660...690 V AC 50/60 Hz (AC-3) 3.7 kW at 400 V AC 50/60 Hz (AC-4) |
|
| motor power HP (UL / CSA) |
0.5 hp at 115 V AC 50/60 Hz for 1 phase motors
2 hp at 230/240 V AC 50/60 Hz for 1 phase motors 3 hp at 200/208 V AC 50/60 Hz for 3 phases motors 3 hp at 230/240 V AC 50/60 Hz for 3 phases motors 7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors 10 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
|
| control circuit type |
DC standard
|
|
| [Uc] control circuit voltage |
110 V DC
|
|
| auxiliary contact composition |
1 NO + 1 NC
|
|
| [Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947
|
|
| overvoltage category |
III
|
|
| [Ith] conventional free air thermal current |
10 A (at 60 °C) for signalling circuit
16 A (at 60 °C) for power circuit |
|
| Irms rated making capacity |
250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
|
| rated breaking capacity |
250 A at 440 V for power circuit conforming to IEC 60947
|
|
| [Icw] rated short-time withstand current |
105 A 40 °C - 10 s for power circuit
210 A 40 °C - 1 s for power circuit 30 A 40 °C - 10 min for power circuit 61 A 40 °C - 1 min for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit |
|
| associated fuse rating |
10 A gG for signalling circuit conforming to IEC 60947-5-1
40 A gG at <= 690 V coordination type 1 for power circuit 25 A gG at <= 690 V coordination type 2 for power circuit |
|
| average impedance |
2.5 mOhm - Ith 16 A 50 Hz for power circuit
|
|
| [Ui] rated insulation voltage |
Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified |
|
| electrical durability |
2 Mcycles 12 A AC-3 at Ue <= 440 V
0.8 Mcycles 25 A AC-1 at Ue <= 440 V |
|
| power dissipation per pole |
0.36 W AC-3
1.56 W AC-1 |
|
| safety cover |
With
|
|
| mounting support |
Rail
Plate |
|
| standards |
CSA C22.2 No 14
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
|
| product certifications |
GOST
LROS (Lloyds register of shipping) DNV UL GL BV RINA CSA CCC |
|
| connections - terminals |
Power circuit: spring terminals 1 cable(s) 2.5 mm²flexible without cable end
Power circuit: spring terminals 2 cable(s) 2.5 mm²flexible without cable end Control circuit: spring terminals 1 cable(s) 2.5 mm²flexible without cable end Control circuit: spring terminals 2 cable(s) 2.5 mm²flexible without cable end |
|
| operating time |
53.55...72.45 ms closing
16...24 ms opening |
|
| safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
|
| mechanical durability |
30 Mcycles
|
|
| maximum operating rate |
3600 cyc/h 60 °C
|
| coil technology |
With integral suppression device
|
|
|---|---|---|
| control circuit voltage limits |
Drop-out: 0.1...0.25 Uc DC (at 60 °C)
Operational: 0.7...1.25 Uc DC (at 60 °C) |
|
| time constant |
28 ms
|
|
| inrush power in W |
5.4 W (at 20 °C)
|
|
| hold-in power consumption in W |
5.4 W at 20 °C
|
|
| auxiliary contacts type |
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1 |
|
| signalling circuit frequency |
25...400 Hz
|
|
| minimum switching current |
5 mA for signalling circuit
|
|
| minimum switching voltage |
17 V for signalling circuit
|
|
| non-overlap time |
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact |
|
| insulation resistance |
> 10 MOhm for signalling circuit
|
| IP degree of protection |
IP20 front face conforming to IEC 60529
|
|
|---|---|---|
| protective treatment |
TH conforming to IEC 60068-2-30
|
|
| pollution degree |
3
|
|
| ambient air temperature for operation |
-5…60 °C
|
|
| ambient air temperature for storage |
-60…80 °C
|
|
| permissible ambient air temperature around the device |
-40…70 °C at Uc
|
|
| operating altitude |
3000 m without
|
|
| fire resistance |
850 °C conforming to IEC 60695-2-1
|
|
| flame retardance |
V1 conforming to UL 94
|
|
| mechanical robustness |
Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz Shocks contactor open: 10 Gn for 11 ms Shocks contactor closed: 15 Gn for 11 ms |
|
| height |
99 mm
|
|
| width |
45 mm
|
|
| depth |
95 mm
|
|
| net weight |
0.485 kg
|
| Sustainable offer status |
Green Premium product
|
|
|---|---|---|
| REACh Regulation | ||
| EU RoHS Directive |
Compliant
EU RoHS Declaration |
|
| Mercury free |
Yes
|
|
| RoHS exemption information | ||
| China RoHS Regulation |
China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information |
|
| Environmental Disclosure | ||
| Circularity Profile | ||
| WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
|
| Warranty |
18 months
|
|---|
Returns Policy
You may return most new, unopened items within 30 days of delivery for a full refund. We'll also pay the return shipping costs if the return is a result of our error (you received an incorrect or defective item, etc.).
You should expect to receive your refund within four weeks of giving your package to the return shipper, however, in many cases you will receive a refund more quickly. This time period includes the transit time for us to receive your return from the shipper (5 to 10 business days), the time it takes us to process your return once we receive it (3 to 5 business days), and the time it takes your bank to process our refund request (5 to 10 business days).
If you need to return an item, simply login to your account, view the order using the 'Complete Orders' link under the My Account menu and click the Return Item(s) button. We'll notify you via e-mail of your refund once we've received and processed the returned item.
Shipping
We can ship to virtually any address in the world. Note that there are restrictions on some products, and some products cannot be shipped to international destinations.
When you place an order, we will estimate shipping and delivery dates for you based on the availability of your items and the shipping options you choose. Depending on the shipping provider you choose, shipping date estimates may appear on the shipping quotes page.
Please also note that the shipping rates for many items we sell are weight-based. The weight of any such item can be found on its detail page. To reflect the policies of the shipping companies we use, all weights will be rounded up to the next full pound.
- "Excellent products and excellent service." - Josephine
- "Excellent value. High quality products at reasonable prices." - Warren
- "Outstanding customer service." - Jack
- "You're the best! Thank you!" - Tatiana