New Factory Sealed - Original product -12 Months Warranty
-12 Item Items
Warning: Last items in stock!
Availability date:
range | ComPacT new generation |
---|---|
product name | ComPacT NSX new generation |
device short name | NSX100S |
product or component type | Circuit breaker |
device application | Distribution |
poles description | 2P |
protected poles description | 2D |
[In] rated current | 50 A at 40 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz 500 V DC |
network type | AC DC |
network frequency | 50/60 Hz |
suitability for isolation | Yes conforming to EN/IEC 60947-2 |
utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity | 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 250 V DC 1 pole conforming to IEC 60947-2 100 kA Icu at 500 V DC 2 poles in series conforming to IEC 60947-2 100 kA Icu at 500 V DC 2P conforming to IEC 60947-2 |
Performance level | S 70 kA 415 V AC |
trip unit name | TM-D |
trip unit technology | Thermal-magnetic |
trip unit protection functions | LI |
control type | Toggle |
Circuit breaker mounting mode | Fixed |
[Ui] rated insulation voltage 750 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2 [Ics] rated service short-circuit breaking capacity 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 250 V DC conforming to IEC 60947-2
100 kA at 500 V DC conforming to IEC 60947-2mechanical durability 20000 cycles electrical durability 20000 cycles at 277 V In/2
10000 cycles at 277 V Inpower dissipation per pole 4.11 W mounting support Backplate mounting position Horizontal and vertical
Flat on the backupside connection Front downside connection Front connection pitch 35 mm protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)trip unit rating 50 A at 40 °C Long-time pick-up adjustment type Ir (thermal protection) Fixed [Ir] long-time protection pick-up adjustment range 1 x In Long-time protection delay adjustment type tr Fixed Instantaneous protection pick-up adjustment type Ii Fixed [Ii] instantaneous protection pick-up adjustment range 500 A earth-leakage protection Without Width (W) 70 mm Height (H) 161 mm Depth (D) 86 mm net weight 1.2 kg