Close
LV429550 View larger

LV429550

Square D (Schneider Electric)

10_1946537620

Square D (Schneider Electric)

3606480008436

New Factory Sealed - Original product -12 Months Warranty

Circuit breaker Compact NSX100B - TMD - 100 A - 3 poles 3d

More details

24 Items

IN STOCK

$321.20

Usually dispatched 1-2 days

Data sheet

Breaking Capacity Code Icu @ 415VB / 25kA
Poles Description3P
Trip Unit Rating100 A
Trip Unit NameTM-D

More info

Characteristics
Main
Commercial StatusCommercialised 
Product or component typeCircuit breaker 
Device short nameCompact NSX100B 
Circuit breaker applicationDistribution 
Poles description3P 
Protected poles description3t 
Network typeAC 
Network frequency50/60 Hz 
[In] rated current100 A ( 40 °C ) 
[Ui] rated insulation voltage800 V AC 50/60 Hz 
[Uimp] rated impulse withstand voltage8 kV 
[Ue] rated operational voltage690 V AC 50/60 Hz 
Breaking capacity code
Breaking capacityIcu 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 
Icu 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 
Icu 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 
Icu 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 
40 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 
20 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 
[Ics] rated service breaking capacityIcs 7.5 kA 500 V AC 50/60 Hz conforming to IEC 60947-2 
Ics 40 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2 
Ics 25 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 
Ics 20 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 
Suitability for isolationYes conforming to IEC 60947-2 
Yes conforming to EN 60947-2 
Utilisation categoryCategory A 
Trip unit nameTM-D 
Trip unit technologyThermal-magnetic 
Trip unit protection functionsLI 
Trip unit rating100 A ( 40 °C ) 
Protection typeOverload protection (thermal) 
Short-circuit protection (magnetic) 
Pollution degree3 conforming to IEC 60664-1 
Complementary
Control typeToggle 
Mounting modeFixed 
Mounting supportBackplate 
Upside connectionFront 
Downside connectionFront 
Mechanical durability50000 cycles 
Electrical durability50000 cycles 440 V In/2 conforming to IEC 60947-2 
30000 cycles 440 V In conforming to IEC 60947-2 
20000 cycles 690 V In/2 conforming to IEC 60947-2 
10000 cycles 690 V In conforming to IEC 60947-2 
Connection pitch35 mm 
Local signallingPositive contact indication 
Long time pick-up adjstment type IrAdjustable 
Long time pick-up adjustment range0.7...1 x In 
Long time delay adjustment typeFixed 
[tr] long-time delay adjustment15 s 6 x Ir 
120...400 s 1.5 x In 
Short-time pick-up adjustment type IsdFixed 
[Isd] short-time pick-up adjustment range800 A 
Short-time delay adjustment typeFixed 
Height161 mm 
Width105 mm 
Depth86 mm 
Product weight2.05 kg 

30 other products in the same category

Schneider Partner

Schneider Electric Authorised distributor

Shipping Partner

DHL Express Delivery

Secure Payments

Scure site globalsign

Close